6  Submarine  cables
6.1  Preliminary  remarks
The  cables  and  accessories  used  must  be  state  of  the  art  and  meet  the  requirements  of  the
relevant  standards  in  each  case  (selection  see  below)  or  their  suitability  must  have  been
proven  by  comparable  tests  and  they  must  be  suitable  for  the  particular  operating  conditions/
applications.
Reference  is  made  to  the  specifications  of  the  Spatial  Offshore  Grid  Plan  (BFO)  in  the  current
version.  Only  one  approval  is  granted  for  the  cabling  within  the  wind  farm  and  the  power  output ­
  cable.

6.2  Technical  codes  of  practice
6.2.1  Cabling  within  the  wind  farm
For  test  requirements  and  suitability  certificates,  the  following  technical  codes  of  practice  in
their  current  version  must  be  complied  with  in  relation  to  alternating  current  transmission  using ­
  plastic-insulated  power  cables  (energy  distribution  cables):
DIN  VDE  0276-620  (VDE  0276-620)
IEC  60502-2  Power  cables  with  extruded  insulation  and  their  accessories  for  rated
voltages  from  1  kV  (U m =  1.2  kV)  up  to  30  kV  (U m =  36  kV)  -  Part  2:
Cables  for  rated  voltages  from  6  kV  (U m =  7.2  kV)  up  to  30  kV  (U m =  36  kV)
DIN  VDE  0278-629-1  (VDE  0278-629-1)
IEC  60502-4  Power  cables  with  extruded  insulation  and  their  accessories  for  rated
voltages  from  1  kV  (U m =  1.2  kV)  up  to  30  kV  (U m =  36  kV)  -  Part  4:
Test  requirements  on  accessories  for  cables  with  rated  voltages  from
6  kV  (U m =  7.2  kV)  up  to  30  kV  (U m =  36  kV)
DIN  EN  61442  (VDE  0278-442)
IEC  61442  Test  methods  for  accessories  for  power  cables  with  rated  voltages
from  6  kV  (U m =  7.2  kV)  up  to  30  kV  (U m =  36  kV)
6.2.2  Connection  to  the  power  grid
6.2.2.1  Alternating  current  transmission
For  test  requirements  and  suitability  certificates,  the  following  technical  codes  of  practice  in
their  current  version  must  be  complied  with  for  alternating  current  transmission  using  plasticinsulated
  low-voltage,  medium-voltage  and  high-voltage  cables:
DIN  VDE  0276-632  (VDE  0276-632)
IEC  60840  Power  cables  with  extruded  insulation  and  their  accessories  for  rated
voltages  above  30  kV  (U m =  36  kV)  up  to  150  kV  (U m =  170  kV)  -  Test
methods  and  requirements
DIN  IEC  62067  (VDE  0276-2067)
IEC  62067  Power  cables  with  extruded  insulation  and  their  accessories  for  rated
voltages  above  150  kV  (U m =  170  kV)  up  to  500  kV  (U m =  550  kV)  -  Test
methods  and  requirements
            